恒溫(wen)恒濕試驗箱壓縮機(ji)損壞的(de)原(yuan)因有哪些?

      1、設備電(dian)(dian)源(yuan)電(dian)(dian)壓(ya)(ya)不(bu)(bu)穩定,電(dian)(dian)源(yuan)電(dian)(dian)壓(ya)(ya)質量不(bu)(bu)好(hao),如電(dian)(dian)壓(ya)(ya)過(guo)高(gao)或(huo)過(guo)低(di),對壓(ya)(ya)縮(suo)機(ji)(ji)電(dian)(dian)機(ji)(ji)有不(bu)(bu)良影響,特別是(shi)超出壓(ya)(ya)縮(suo)機(ji)(ji)額定電(dian)(dian)壓(ya)(ya)范圍(wei)使用不(bu)(bu)當,長期運(yun)行(xing)使壓(ya)(ya)縮(suo)機(ji)(ji)電(dian)(dian)機(ji)(ji)處于低(di)效過(guo)熱狀態(tai),導致絕緣(yuan)不(bu)(bu)良,電(dian)(dian)機(ji)(ji)燒毀(hui)。而(er)且,如果是(shi)三(san)相電(dian)(dian)壓(ya)(ya)或(huo)電(dian)(dian)流不(bu)(bu)平衡也(ye)會(hui)導致電(dian)(dian)機(ji)(ji)損(sun)耗(鐵損(sun)耗和銅損(sun)耗)增加,壓(ya)(ya)縮(suo)機(ji)(ji)電(dian)(dian)機(ji)(ji)線圈溫度(du)過(guo)高(gao),過(guo)熱器保護不(bu)(bu)當,壓(ya)(ya)縮(suo)機(ji)(ji)電(dian)(dian)機(ji)(ji)絕緣(yuan)燒毀(hui)。
 
     2、恒溫恒濕試驗箱壓縮機旋轉部件被卡住。壓縮機卡住是由于壓縮機內有異物進入、拋油不潤滑、零件松動、過熱燒結、軸承磨損等原因造成的,而在這種情況下,如果壓縮機保護動作失靈,可能會過載燒毀。
 
     3、恒溫恒濕試驗箱接觸器故障接觸器容易選擇不當或質量差,導致接觸電阻過大或燒結,導致電機短路燒結。

 4、系統清潔度不夠。如果有水進(jin)入堆積,水、制冷(leng)劑和(he)冷(leng)凍油在系統中循環(huan)。經過高溫和(he)低(di)溫的(de)變化,會(hui)產生酸性物質,進(jin)而破壞電(dian)機的(de)絕緣層長期運行(xing)會(hui)導致電(dian)機絕緣不良(liang),從而燒(shao)毀壓縮機。

     5、如果您這邊已經有更換新的壓縮機,那么對于曾經有恒溫恒濕試驗箱壓縮機燒毀故障的系統,必須定期清洗,因為壓縮機燒毀時會產生強酸,并停留在系統中。如果處理不干凈,新壓縮(suo)機運行后,殘留(liu)的酸性(xing)物(wu)質會腐蝕電(dian)機絕緣層,導(dao)致(zhi)新壓縮(suo)機再(zai)次燒毀故障哦。